EPR Insulated, LSZH Sheathed Cable, 600/1000V, IEC60502-1
Construction
Conductor: Plain annealed flexible copper, Class 5 stranded circular
Insulation: Ethylene Propylene Rubber (EPR)
Insulation colour:
2 Cores: Brown, Blue
3 Cores: Brown, Blue, Green/Yellow
4 Cores: Brown, Black, Grey, Green/Yellow
5 Cores: Brown, Black, Grey, Blue, Green/Yellow
Outer Sheath: Cross-linked Low Smoke Zero Halogen (LSZH) Compound with Anti-Termite Characteristic and UV Resistant
Outer Sheath Colour: Black / Other colour upon request
Electrical Characteristics
Operating voltage, U0/U: 600/1000V
Operating temperature: -15°C to +90°C
Final short circuit temperature: 250°C
Test Voltage: 3.5kV for 5 minutes
Reference Standards
Design Specification: IEC60502-1
Conductor: IEC60228, BS EN60228
Flame retardancy: IEC60332-3-24, BS EN60332-3-24
Low Smoke Zero Halogen: IEC61034-2, BS EN61034-2, IEC60754-1, IEC60754-2, BS EN60754-1, BS EN60754-2
Installation Reference
Minimum bending radius (mm): 6 x cable overall diameter
Maximum pulling tension: 15N/mm²